Content: Pagemaster:
|
Pacific
Region Fires - 2000 February 11, 2000 - Arguello, Inc.
Remarks: A line containing heat medium leaked at a loose flange onto the turbine exhaust. The heat of the exhaust ignited the heat medium, creating a small fire. The fire was quickly extinguished with a fire extinguisher. The investigation findings showed that the turbine and heat package had been out of service for about 9 months. It was recommended that the bolts on the flange and other heat packages be tightened. The investigation also showed that the operator committed an OCS violation by not notifying the District Supervisor of the occurrence in a timely manner. July 7, 2000 - Arguello, Inc.
Remarks: A small fire occurred at the exhaust of the turbine at sales gas compressor "C." Lube oil leaked at a tubing fitting, resulting in oil soaked insulation, which came in contact with the hot turbine exhaust and caused a small fire. The fire was extinguished immediately.
Home | Search | Topic Index | About MMS | What's New Offshore Home | Offshore Safety | Offshore Stats and Facts | OCS-Related Incidents
Abbreviations |
Collisions |
Crane Incidents |
Explosions |
Fatalities |
Fires |
Injuries | Privacy Act/Disclaimers | Revenues Last Updated: 03/31/04, 01:01 PM |