ADMINISTRATIVE MESSAGE ROUTINE R 141557Z FEB 97 ZYB FM COMNAVSURFPAC SAN DIEGO CA//N01// TO NAVSURFPAC AFLOAT UNCLAS //N05100// MSGID/GENADMIN/COMNAVSURFPAC N41// SUBJ/SILVER-PLATED FUSE FERRULES// REF/A/DOC/NSTM/01FEB96// AMPN/REF A IS NSTM CH. 300R3, PARA 300-2.5.4.1, USE OF SILVER-PLATED FUSE FERRULES AND FUSE CLIPS PREVENT CORROSION// POC/T. STEFANIK/CNSP N418-/TEL:DSN 577-3070:(619)437-3070// RMKS/1. REF A PROVIDES INFORMATION ON THE USE OF SILVER-PLATED FERRULES TO MINIMIZE CORROSION BETWEEN FUSE FERRULES AND FUSE CLIPS. CORROSION PREVENTION IS CRITICAL TO PREVENT HIGH RESISTANCE AND LOCAL HEATING THAT CAN CAUSE FUSE LINKS TO MELT. 2. PRESINSURV REPORTS A NUMBER OF SHIPS STILL USING NICKEL AND BRASS FERRULE FUSES. SHIPS ARE TO IMPLEMENT CHANGE OUTS PER REF A. 3. SHIPS SHOULD MAKE EVERY EFFORT TO REPLACE NICKEL AND BRASS FERRULE FUSES USING THE FOLLOWING PRECEDENTS: A. FUSES WITH SILVER-PLATED FERRULES SHOULD BE MATCHED WITH SILVER-PLATED FUSE CLIPS. THIS IS IDEAL CORROSION PREVENTION BUT IS NOT ALWAYS POSSIBLE. B. FUSES WITH SILVER-PLATED FERRULES CAN BE USED IN CONJUNCTION WITH BRASS FUSE CLIPS. C. SHIPBOARD ELECTRONIC EQUIPMENT MAY BE DESIGNED WITH NON-SILVER FERRULE FUSES. THIS WOULD BE AN EXCEPTION AND AN AUTHORIZED USE OF BRASS FUSES AND CLIPS. OTHER SITUATIONS MAY BE THE PURCHASE OF COMMERCIAL TYPE EQUIPMENT EMBELLISHED WITH BRASS FUSES. 4. ANY FUSE REPLACEMENTS MUST FOLLOW SAFETY PRECAUTIONS FOUND IN REF A, NSTM PARA 300-2.5.4. IN ADDITION, FUSE CLIP REPLACEMENTS SHOULD BE A GRADUAL INSTALLATION BASED UPON MANPOWER, EASE OF ACCESS OR MAINTENANCE SCHEDULES. 5. BOTTOM LINE: ONCE SILVER-PLATED FERRULES AND CLIPS ARE IN PLACE, REPLACE WORN COMPONENTS ONLY WITH SILVER-PLATED AND NEVER BRASS OR NICKEL FUSE FERRULES OR FUSE CLIPS.// BT